EZ Path® Estimator

Select your cable size from the left-hand columns to determine maximum capacity of pathways.

Cable Diameter Pathway Cable Capacity
mm inches EZD22
Series
EZD33
Series
EZD44+
Series
3 0.118 80 352 868
3.5 0.138 63 266 648
4 0.157 42 192 483
4.5 0.177 35 154 378
5 0.197 30 130 304
5.5 0.217 20 108 255
6 0.236 20 88 210
6.5 0.256 12 70 168
7 0.276 12 63 156
8 0.315 9 48 110
9 0.354 6 35 90
10 0.394 6 30 72
11 0.433 4 24 56
12.5 0.492 4 20 42
15 0.591 2 12 30
18 0.709 1 6 20
20 0.787 1 6 16
25 0.984 1 4 9
30 1.181 0 2 6
35 1.378 0 1 4

Use this quick and easy calculator to figure out the size and number of EZ-Path sleeves required for each barrier penetration.

NOTE: This calculator assumes use of cable installation practices that maximize path utilization. The calculated results should be considered the minimum required. Download Maximize EZ-Path Capacity to identify additional factors that may influence the number of pathways required for your installation

1. Select your cable size by clicking the cable diameter at left.

2. Enter the number of cables you will be installing now.

3. Enter a value for cables you may be adding in the future


Cables Now:
Cables Future:


IMPORTANT NOTICE: The information herein is theoretical and is provided for infomational purpose only. Variations in cable size and shape, as well as cable bundle size and other factors may influence these calculations. Therefore, THE ACCURACY OF THIS INFOMATION CANNOT BE GUARANTEED.
U.S. Patent 6,732,481